Widespread corrosion in LTHW and CHW systems

Widespread corrosion in LTHW and CHW systems

 

Building: Large Business Park

Manifestation: Blockage of pipework, failure of boilers and condenser coils

Cause: Insufficient installed expansion capacity and poor maintenance of system pressures leading to large water losses with consequent gross aeration of system water and loss of inhibitors.

Solution: Remedial flushing of pipework where possible but large replacement of pipework and system components necessary. Installation of larger expansion vessels and increase to system pressure.  Proper maintenance regime introduced.

 

 

Widespread corrosion in LTHW and CHW systems2

Copyright © 2011 Midland Corrosion Services Ltd Site by PigeonTech